Features |
|
Compliance | Standards: EN 60079 – 0, IS/ IEC / EN 60079 – 30 – 1 & EN 60079 – 31. |
Approvals |
Tested by Central Institute of Mining and Fuel Research (CSIR-CIMFR), Dhanbad and approved by Petroleum and Explosives Safety Organization ( PESO), Nagpur, India for Zone II , TI (ATEX) for Zone I / Division II & EAC for use in hazardous area applications. |
Safety | As the Cable self regulates its heat output, its limit the maximum sheath temperature, thus making it burnout proof. |
Specifications |
||||
Catalogue Reference | HTT15 | HTT30 | HTT45 | HTT60 |
Heating Power W/m (230V AC) at 10 C | 15 | 30 | 45 | 60 |
Voltage Supply | 230/240VAC, 50/60 Hz, 110/120VAC, Max. 500V on request. | |||
Max. Installation Temperature Power On | 230℃ | 180℃ | 165℃ | 150℃ |
Max. Exposure Temperature Power Off | 260℃ | |||
Min. Installation Temperature | -65℃ | |||
Minimum Bending Radius | 25mm | |||
Dimensions | Approx. 8.00 x 11.75 mm |
# Thermopads reserves the right to modify the specifications in line with future improvements, updated standards or updated certifications
HTT Power Output Characteristics
Circuit Breaker Selection and Maximum Circuit Lengths
Catalog Number | Output at 100C, 230 V | Max. Circuit Length | Circuit Breaker Size | Max. Maintenance Temperature |
Unconditional Maint. Temp T Rating at Max. Temp |
HTT-15 | 15 W/m | 170 | 16A | 2300C | T2 |
270 | 25A | ||||
HTT-30 | 30 W/m | 84 | 16A | 1800C | T3 |
130 | 25A | ||||
180 | 32A | ||||
190 | 40A | ||||
HTT-45 | 45 W/m | 55 | 16A | 1650C | T3 |
90 | 25A | ||||
120 | 32A | ||||
155 | 40A | ||||
HTT-60 | 60 W/m | 45 | 16A | 1500C | T3 |